Selecting The Grid Disconnecting Device; Selecting The Dc Input Disconnecting Device; Compatibility Of The Solar Generator And Inverter - ABB PVS800-57B Hardware Manual

Solar central inverters
Hide thumbs Also See for PVS800-57B:
Table of Contents

Advertisement

The inverter does not require a specific transformer notation. ABB recommends using
traditional notations, such as Dy11d0, etc.
The AC side of the inverter is designed only for IT (floating) networks, do not ground the
neutral (star) point of the transformer on the inverter side or connect it to the neutral points
of other windings.

Selecting the grid disconnecting device

The inverter is equipped with a hand-operated grid disconnecting device or an AC breaker
which isolates the inverter and the solar generator from the electrical power system. The
grid disconnecting device does not isolate the AC output busbars or internal auxiliary
transformers from the electrical power system. Before you do installation and maintenance
work on the inverter, isolate the AC output cables and busbars from the electrical power
system with an AC disconnector outside the inverter, for example, an HV breaker on the
HV side of the transformer.
Refer to
Ratings
on page
correct current and voltage dimensioning for each product. If you do not know the
installation-specific short-circuit current of the grid, use the value in
specification
on page
disconnecting device. The grid disconnecting devices must be lockable.

Selecting the DC input disconnecting device

As standard, the inverter has a hand-operated DC input disconnecting device. The DC
input disconnecting device does not isolate the DC input conductors or terminals of the
inverter from the input voltage. The junction boxes must have breakers for the isolation or
other suitable devices between the PV generator and inverter, for example, a separate
disconnector box.
Refer to
Ratings
on page
current and voltage dimensioning for each product. If you do not know the installation-
specific short-circuit value for each DC-side DC input disconnecting device, refer to
input connection data
input disconnecting devices. Make sure that the DC-side DC input disconnecting devices
can handle the back feed current. The DC input disconnecting devices must be lockable.

Compatibility of the solar generator and inverter

Make sure that:
The current and voltage of the generator match the rated values of the inverter.
The open circuit voltage of the generator does not exceed the maximum allowed DC
voltage of the inverter.
The operating range of the generator is between the limits of the maximum power
point tracking (MPPT) function of the inverter control program.
The grounding requirements of the generator match the inverter.
46
and
AC output connection specification
53
for adequate short-circuit current capability of the grid
46
and
DC input connection data
on page
54
for adequate short-circuit current capability of the DC
Planning the electrical installation 35
on page
AC output connection
on page
54
for the correct
53
for the