7 How to Programme the Frequency Converter

7.1.1 DC-link Compensation Disabling

The FC series include a feature which ensures that the output
voltage is independent of any voltage fluctuation in the DC
link, e.g. caused by fast fluctuation in the mains supply
voltage. In some cases this very dynamic compensation can
produce resonances in the DC link and should then be
disabled. Typical cases are where AHF005/010 is used on
supply grids with high short circuit ratio. Fluctuations can
often be recognized by increased acoustical noise and in
extreme cases by unintended tripping. To prevent
resonances in the DC-link, it is recommended to disable the
dynamic DC-link compensation by setting 14-51 DC Link
Compensation to off.
7
7
14-51 DC Link Compensation
Option:
[0]
Off
[1]
On
*
56
AHF005/010 Design Guide
Function:
Disables DC Link Compensation.
Enables DC Link Compensation.