VI. COMMAND LINE INTERFACE (CLI) PROTOCOL
The Command Line Interface provides complete setup of all functions of the AR. The CLI may be accessed through the Telnet
protocol, and requires a Telnet client program. Some commands of the CLI require administrative rights; these are indicated in the
following tables.
Notes:
Telnet negotiations require sending these bytes when first connecting: (0x) FF FD 01 FF FD 03 FF FB 1F FF FB 18 FF FB 20
Every command must be followed by a Carriage Return and Line Feed: (0x) 0D 0A
Prompt
User>
Password>
Axess Ready>
Axess Ready Reboot Required>
Command
get outlet
set outlet < on | off | cycle >
Command
get location
set location < 20-character max >
get cycle
set cycle < 1-999 >
get upgrade enable
set upgrade enable < yes | no >
logout
reboot
© 2019 AMETEK Electronic Systems Protection | Technical Support 1-800-645-9721 | surgex.com
SA-20-AR
Description
Prompts the user to enter the user name (either user or admin).
Prompts the user to enter the password.
Prompt displayed while logged in.
Prompt displayed after changes have been made that require a reboot. This prompt will
remain active until the AR has been rebooted.
Description
Returns the current status of the outlet.
Sets the outlet to the selected state.
Description
Returns the location ID.
Sets the location ID.
Returns the cycle time currently in use in seconds.
Sets the cycle time in seconds.
Returns the upgrade enable status.
Enables or disables the ability to upload new firmware.
Terminates the telnet session.