Toshiba TOSVERT VF-S15 Instruction Manual page 34

My function-s
Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

Input
Parameter
setting
setting
Traverse deceleration
 
in progress
Parts replacement
 
alarm
Over-torque detection
 
pre-alarm
Frequency setting
 
mode selection 1/2
Panel / remote
 
selection
Forced continuous
 
operation in progress
Specified frequency
 
operation in progress
Signal in accordance
 
of frequency command
Fault signal (output
 
also at a retry waiting)
PTC input alarm signal ON: PTC thermal input value is 60% of f646 or more
 
Safe torque off signal
 
Analog input break
 
detection alarm
F terminal state
 
R terminal status
 
Cooling fan
 
replacement alarm
Number of starting
 
alarm
Acceleration operation
 
in progress
Deceleration operation
 
in progress
Constant speed
 
operation in progress
DC braking in
 
progress
 
Factory specific
 
coefficient
 
Integral input power
 
pulse output signal
Shock monitoring
 
pre-alarm signal
Function
ON: Traverse deceleration in progress
ON: Any one of cooling fan, control board capacitor, or main circuit
capacitor reaches parts replacement time
ON: Torque current is 70% of f616 setting value or more
OFF: less than f616x70%-f619
ON: Select frequency setting mode selection 2 (f207)
OFF: Select frequency setting mode selection 1 (fmod)
ON: Operation command is panel
ON: Forced continuous operation in progress
ON: Specified Frequency operation in progress
ON: Frequency commanded by f389 and f369 are within
±f167
ON: While inverter is tripped or retried
OFF: less than 60% of f646
ON: Safe torque off signal output
ON: VIB terminal input value is f633 or less
OFF: more than f633
ON: terminal F is ON state
ON: terminal R is ON state
ON: Cooling fan reaches parts replacement time
ON: Number of starting is f648 or more
ON: Acceleration operation in progress
ON: Deceleration operation in progress
ON: Constant speed operation in progress
ON: DC braking in progress
Do not set the value. The function is for manufactuer setting.
ON: Integral input power unit reach
ON: Current / torque value reach the shock monitoring detection
condition
Operation output specifications (in case of positive logic)
- 33 -
E6581865