2 Installation and commissioning

2.5.17 Connection of servo disconnect, by servo power switch

2.5.17 Connection of servo disconnect, by servo power switch
General
The IRC5 controller is pre-wired to accept a customer servo disconnect.
Location
The contactor is found on the left hand side inside the controller as shown below.
xx0400001058
A
B
C
D
E
Required equipment
The table below details the required equipment.
Equipment
Wire
Switch
Standard toolkit
Circuit diagram
Continues on next page
102
Note
Due to risk of voltage drop, the switch to the servo disconnect circuit should not
be mounted more than 50 meters from the Drive Module.
A
MOTOR ON contactor K42 / K43
Contactor block3
Brake contactor
Jumper (4 pcs)
Contactor interface board
© Copyright 2004-2018 ABB. All rights reserved.
B
C
D
E
Note
AWG 10, brake AWG 16
500V 40 A, brake 24V 10A
See
Circuit diagrams on page
325.
Product manual - IRC5
3HAC047136-001 Revision: M