Electrical Connection Of The Outdoor Unit - iDM iPump A 3-11 Technical Documentation Installation Instructions

Model: 400 v, 230 v with navigator 2.0. air heat pump with inverter-technology
Hide thumbs Also See for iPump A 3-11:
Table of Contents

Advertisement

8. Electrical assembly
electrical assembly
8 .5. Elec tr ic al con n e c t ion of t h e out do o r u n it
For the electrical connection of the outdoor unit
viewed from the front, the cover on the left side must
be removed. The electrical lines will be layed from
below to the connection box of the ventilator.
Electrical connection according to the enclosed wiring
diagram.
Remove the cover
Electrical connection box
for the ventilator
The circuit breaker for the main current connection (Q1) and the circuit breaker for the immersion
heater (Q2) are in the electric pan of the iPump. To use the switches, the front part of the iPump
must be removed. The control current for the outdoor unit is routed over the indoor unit. For the data
transfer, an shielded cable must be used. The electrical connection must be done according to the
wiring diagram.
Outdoor unit
36
Control current 3x1.5mm², 1x230V
Data cable Li2YCYv 2x2x0.5mm²
Wall opening
Refrigerant connection pipes
Installation instructions iPump A 3-11
Connecting line from the indoor unit to the out-
door unit
The power supply of control for the outdoor unit will
be energised via the indoor unit. In addition, a data
cable must be routed.
Control current: ÖLFLEX CLASSIC 100 BK 5G1.5
Bus-connection: Li2YCYv(TP) 2x2x0.5 mm²
The connecting cable between the main
board and the control unit will be connec-
ted during commissioning. If the front part
must be removed in case of maintenance,
there may be damages to the connections
of the control unit or the main board by
careless and rapid remove.
If the iPump should be connected to my-
iDM (Network), the network cable must
be provided on site.
The wiring may only be done by a
qualifi ed electrician in accordance to the
enclosed wiring diagram.
Indoor unit
Main current 3+N 400 V
1+N 230 V
Control current 1x230 V
F = B13A
Power line heating element
3+N 400 V, 1+N 230 V
Network cable