7. Connection of the refrigerant circuit

7. Connection of the refrigerant circuit
Connection of the refrigerant circuit
7 .1. Co n n ec ti on li n es of t h e re f rig er ant ci r -
cui t
The outdoor unit is connected to the refrigerant circuit
of the indoor unit via two steam diffusion-sealed in-
sulated copper pipes of air-conditioning pipe quality.
The maximum length of the pipes are 20 m in one
direction.
To avoid buckles in the refrigerant pipes, the mi-
nimum bend radius must be observed. To prevent
embrittlement or fractures, a pipe location must never
be bent twice. The bend radius should not be less
than 100 - 150 mm.
The connection pipes between indoor
unit and outdoor unit are not included
in the delivery. They are available as an
accessory and can be ordered by the
iDM-dealer.
Dimension of the refrigerant pipes
Liquid line 12 mm
Hot gas line 16 mm
On the refrigerant side the indoor unit and the outdoor unit of the iPump A 3-11
are „hermetically tight".
Open refrigerant pipes must be protected against moisture and dirth with caps or tapes.
Refrigerant pipes may not be buckled or crushed!
32
Installation instructions iPump A 3-11
7. 2 . Co nne ct i o n o f t he o u t do o r u ni t o n r e fri -
g e r ant s id e
The refrigerant pipes are factory-fi tted with protective
caps. Before soldering the refrigerant connection
lines, check that the two shut-off valves are fully
closed. For connecting the refrigerant lines, the pro-
tective caps must be cut with a pipe cutter.
The soldered connections must be made according
to the requirements of the cooling technology by a
trained refrigeration engineer licensed by IDM-Ener-
giesysteme GmbH.
The refrigerant connection pipes must be cut to the
required length using a pipe cutter, and the inner and
outer burrs must be removed with a special deburrer.
The soldering must be performed under protective
gas (nitrogen N2).