12.5 Information on insulation, protection class, degree of protection and rated voltage

12.5
Information on insulation, protection class, degree of protection and
rated voltage
Insulation
The insulation is designed according to the requirements of EN 61131-2: 2007.
Note
In the case of modules with 24 V DC (SELV/PELV) supply voltage, galvanic isolations are
tested with 707 V DC (type test).
Note
The ground/minus pole of the 24 V DC power supply is connected via the device with
functional ground (FE).
Pollution degree / overvoltage category according to IEC 61131
● Pollution degree 2
● Overvoltage category: II
Protection class in accordance with IEC 61131-2:2007
The distributed I/O system ET 200SP fulfills protection class I and includes parts of
protection class II and III. The CPU 1515SP PC2 is a part of protection class III.
The grounding of the mounting rail must meet the requirements for functional earth FE.
The installation location (e.g. enclosure, control cabinet) must have a protective conductor
connection that meets the standard to maintain protection class I.
Degree of protection IP20
Degree of protection IP20 according to IEC 60529, i.e.:
● Protection against contact with standard probe
● Protection against foreign objects with diameters in excess of 12.5 mm
● No protection against water
76
CPU 1515SP PC2 (F/T/TF)
Operating Instructions, 09/2018, A5E42603425-AA