General technical data
7.6 Specifications for Nominal Line Voltages, Isolation Tests, Protection Class, and Degree of Protection
Climatic environmental conditions
Climatic environmental conditions for the operation of fail-safe signal modules:
Environmental conditions
Temperature:
Horizontal mounting position:
Vertical mounting position:
Relative humidity
Air pressure
Pollutant concentration
7.6
Specifications for Nominal Line Voltages, Isolation Tests, Protection
Class, and Degree of Protection
Rated operating voltages
The fail-safe signal modules operate at a rated voltage of 24 VDC; tolerance = 20.4 VDC to
28.8 VDC.
We recommend using power supplies of the Siemens "SITOP power" series.
Test voltages
The isolation test to IEC 61131-2 and the following:
Circuits with rated voltage V
Protection class
Protection class I to IEC 60536 (VDE 0106, Part 1), that is, the mounting rail must be bonded
to ground!
70
Fields of application
from 0°C to 60°C
from 0°C to 40°C
from 5 to 95 %
1080 hPa to 795 hPa
SO
: < 0.5 ppm;
2
Relative humidity < 60%,
no dewing
H
S: < 0.1 ppm;
2
Relative humidity < 60%,
no dewing
to other circuits or
in
ground
0 V < V
≤ 50 V
in
—
No condensation; corresponds to
relative humidity (RH) stress level
2 to IEC 61131-2
Corresponds to an altitude of
-1000 m to 2000 m
Test:
10 ppm; 4 days
1 ppm; 4 days
Test voltage
500 VDC
Installation and Operating Manual, 01/2010, A5E00085586-10
Comments
Fail-safe signal modules