Commissioning
8.3 Initial commissioning an open controller
Creating the configuration
To create the configuration in the TIA Portal, follow these steps:
1. Double-click "Add new device" in the project tree.
2. Select "PC systems > SIMATIC S7 Open Controller > ET 200SP Open Controller >".
3. Select the required device.
4. Select the desired version and click "OK".
5. The following interfaces can be seen in the Open Controller:
– Onboard interface X2 (GB Ethernet Windows interface) that is assigned directly to the
– Exchangeable BusAdapter that is assigned directly to the Software Controller (2 ports)
6. The following preconfigured components can be seen in the device view:
– CPU 1515SP PC2 / CPU 1515SP PC2 F/T/TF: CPU 1505SP (F/T/TF) Software
– CPU 1515SP PC2 + HMI / CPU 1515SP PC2 F + HMI: CPU 1505SP (F) Software
7. Insert the server module from the hardware catalog.
The server module forms the termination of the CPU with the I/O modules. If no server
module is configured, the server module is added automatically during compiling.
8.3.2
Setting the IP address
Set the IP address as follows:
● BusAdapter [X1]: The configured IP address becomes effective on the Open Controller
after a download. To go online via the [X1] interface, the configured address must match
the [X1] address entered in the panel of the software controller.
● Onboard interface [X2]: The configured IP address should be identical to the Windows
IP address of the Open Controller.
8.3.3
Changing the properties of the S7-1500 Software Controller
Information on the property of the CPU is available in the Inspector window under
"Properties". You can change these properties if required.
46
The configured Open Controller is displayed in the device view.
PC station (1 port)
Controller
Controller and WinCC Runtime Advanced
CPU 1515SP PC2 (F/T/TF)