Trigger Subsystem; Trigger[:Immediate] - Agilent Technologies E1339A User's And Scpi Programming Manual

72-channel open collector digital output/relay driver module
Table of Contents

Advertisement

Syntax

TRIGger[:IMMediate]

Comments
Example
86 Relay Driver Module Command Reference
The TRIGger command subsystem controls the triggering operation of a Relay
Driver Module in a switchbox.
TRIGger
[:IMMediate]
:SOURce <source>
:SOURce?
Causes a trigger event to occur when the defined trigger source is
TRIGger:SOURce BUS or TRIGger:SOURce HOLD. This can be used to trigger a
suspended scan operation.
Executing the TRIGger[:IMMediate] Command: A channel list must be
defined with [ROUTe:]SCAN < channel_list > and an INITiate[:IMMediate]
command must be executed before TRIGger[:IMMediate] will execute.
BUS or HOLD Source Remains: If selected, the TRIGger:SOURce BUS
or TRIGger:SOURce HOLD commands remain in effect after triggering a
switchbox with the TRIGger[:IMMediate] command.
Related Commands: INITiate, [ROUTe:]SCAN, TRIGger:SOURce
Example: Advancing Scan Using TRIGger
This example uses the TRIGger command to advance the scan of a single-module
switchbox from channel 00 through 03. Since TRIGger:SOURce HOLD is set, the
scan is advanced one channel each time TRIGger is executed.
TRIG:SOUR HOLD
SCAN (@100:103)
INIT
loop statement
TRIG
increment loop

TRIGger Subsystem

!Sets trigger source to HOLD
!Defines channel list
!Begin scan, close channel 00
!Start count loop
!Advance scan to next channel
!Increment loop count