36 Using the Relay Driver Module
1. Close the first channel SET and open the first channel RESET
2. Wait for the 30 msec timer
3. Turn off the first channel SET current output
4. Wait for the 30 msec timer
5. Close the first channel RESET
6. Wait for the 30 msec timer
7. Turn off the first channel RESET current output
8. Wait for the 30 msec timer
9. Repeat steps 1 - 8 for next channel, to the end of the channel_list
10. If ARM:COUNt >1, repeat steps 1 - 9 for ARM:COUNt number
If TRIG:SOUR IMM is set, the delay time between channel actuations is
120 msec. If another TRIG source is used and the time between triggers is
at least 120 msec, the scan advances when the trigger is received. If another
TRIG source is used and the time between triggers is <120 msec, a "Trigger
Ignored" error is generated.