Maytag MFS80 Installation Instructions Manual page 11

Commercial washer
Table of Contents

Advertisement

Residual Current Device (RCD)
In some countries an RCD is known as an "earth leakage trip,"
"Ground Fault Circuit Interrupter" (GFCI), "Appliance Leakage
Current Interrupter" (ALCI), or "earth (ground) leakage current
breaker."
Specifications:
Tripping current: 100mA (if locally not available/allowed use
a 30mA trip current, preferably selective type with small time
delay set).
Install a maximum of two (2) washers on each RCD
(for 30mA, only one (1) washer)
Type B. There are components inside the washer which use
DC-voltages, making a "Type B" RCD necessary.
NOTE: Type B performs better than Type A, and Type A is
better than Type AC.
When locally allowed, an RCD must always be installed. In some
electrical network earthing systems (IT, TN-C,...), an RCD might
not be allowed (see also IEC 60364).
The washer control circuits are mostly supplied by a separating
transformer. Therefore, the RCD may not detect faults in the
control circuits (but the fuse(s) of the separating transformer will).
Supply Protection Device
A supply protection device keeps the washer and wiring from
experiencing overloads and short circuits. As a supply protection
device, you can use either glow-wire fuses or automatic circuit
breakers. See "Technical Specifications" for the rating of the
nominal current and other specifications of the supply protection
device. This table specifies that protection must be the "slow"
type, curve D for circuit breakers. Although not recommended,
if you cannot use a "slow" type, select the protection device with
one (1) step higher nominal current rating to avoid disconnecting
during start-up.
Supply Cable
The supply cable is not delivered with the washer.
Specifications:
Use conductors with copper cores.
Stranded conductors (flexible wiring) are strongly
recommended to avoid conductor breaking due to vibration.
The cross section depends on the used supply protection
device. See "Manufacturer's Recommended Minimal
Conductor Section" in "Electrical Requirements" for the
minimal cross section.
The cable should be as short as possible, directly across
from the supply protection device to the washer without
branching off.
Do not use a plug or extension cords; the washer is intended
to be permanently connected to the electrical network.
Connection:
Insert the cable through the hole on the rear panel.
Use a strain relief to secure the supply cable.
Strip the conductor ends according to "Adaptation of
Conductor Ends of Supply Cable" illustration on the right.
The protective conductor must be longer to ensure it
is the last one disconnected if the cable is pulled out
unintentionally.
With stranded conductors, it is recommended to use
"wire-end tubes" with an insulated sleeve (6) for L1/U,
(L2/V), (L3/W), (N) conductors. Make sure there cannot be
unintentional contact, since the supply cable stays under
voltage even when the main switch is off.
Crimp a ring terminal (eyelet) to the protective conductor for
good connection to the PE terminal.
Connect the supply cable conductors to the terminals
(main switch [1]) marked with L1/U, (L2/V), (L3/W), (N),
and the terminal (copper screw) marked with PE.
See "Main Power Inlet Connection" illustration below.
Provide a sag in the cable, in front of the cable strain relief.
This will stop condensed water from entering the washer.
See "Main Power Inlet Connection" illustration below.
Adaptation of Conductor Ends of Supply Cable
1. Protective conductor
2. Phase conductor
3. Phase conductor
4. Phase conductor
Main Power Inlet Connection
1. Main switch
2. Strain relief
3. Sag of inlet cable
1
2
3
5. Neutral conductor
6. Wire-end tube
7. The stripped length of
conductors
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mfs180Mfs125Mfs100Mfs275Mfs230

Table of Contents