JX2-CNT1
6.6
Fig. 7: Single-channel counter
The single-channel counter is connected to terminal blocks X21.S and X21.0V (see
Fig. 8).
6.6.1
Terminal Specifications
•
•
•
•
•
•
Connecting Cable Specifications
•
Cable Shielding
Make sure that the signal lines are shielded (see Fig. 6):
•
Jetter AG
Single-Channel Counter
X21
S 0V
STR
0V
REF
INPUT
Jetter
ENCODER
JX2-CNT1
REF
K1
K2
K0
S
X61
Description of Connections
5-pole terminal block COMBICON RM 5.08 (for printed circuit boards)
Cable cross-sectional area: 0.25 - 2.5 mm
Torque (for input plug screws): 0,5 .. 0.6 Nm
The maximum stripping length for input lines is 7 mm.
The accepted VDE guidelines must be followed
Bladed screw-driver: 0.6 x 3.5 x 100 mm
Not needed
Clamp the shield with the greatest possible surface area under the grounding
clamp and establish an electroconductive connection with the grounding block.
6.6 Single-Channel Counter
2
35