Connecting-up
P24
Emerg.
stop
A1
Y10 Y11 Y12
Y21 Y22 13
23
3TK2828
A
Y33 Y34
PE
14
24
2
K1
M
7-14
The checkback contacts of the safety relay are capable of at least
100,000 switching cycles at the specified load (30 V DC / 1 A). The
mechanical service life is about 10
an important component in ensuring reliability and availability of the
machine. For this reason, the pcb with the safety relay must be
replaced in the case of malfunction. In this case, the unit must be
returned for repair or replaced. Function checks must be carried out at
regular intervals, which must be defined in compliance with Employer's
Liability Insurance Regulation BGV A3 §39, para. 3. Accordingly,
function checks must be performed as required by the relevant service
conditions, but at least once a year and additionally after initial
commissioning and any modification and/or maintenance work.
open
closed
-S1
31
47
57
A1
3TK2828
32
48
58
Y33 Y34
Reset
S3
-K1
Fig. 7-6
Sample application of "safe stop" function with contactor safety
combination for monitoring a moving protective device in Safety Category
3 to EN 954-1
6
switching cycles. The safety relay is
Request protective
device enable
S2
K2
-Y1
Y10
13
23
31
47
Y11 Y12
Y21 Y22
A
PE
14
24
32
48
2
X: Binary input, connect to OFF3
e. g. X101.8 --> P558 = 21
Y: Binary output, connect to "Comparison value
reached"
e. g. X101.6 --> P654 = 120; P796 = 0 (comparison value)
Operating Instructions
08.2009
K2
Main switch
57
58
X9
3
4
P2
5
4
6
M
X101
X
OFF3
Y
n = 0
-Cu control
board
SIMOVERT
-K2
MASTERDRIVES
OFF1
6SE7087-6JD50
Siemens AG
SIMOVERT MASTERDRIVES
Mains
-Q1
K1
U1 V1 W1
PV
U2 V2 W2
M
3