Toshiba 1400SE Series Operation Manual page 16

Single phase - .6/.8/1.0/1.2/1.5/2.0/2.4 kva, single phase - .6/.8/1.0/1.5 kva plus
Table of Contents

Advertisement

TOSHIBA
4.0
Specifications
4.1
Standard Series Specifications (Cont'd)
Input
Battery
Battery backup time when fully charged
with 0.7 power factor at77° F (25° C)
Output
Output voltage regulation
Output voltage waveform
Rated load power factor
Voltage transient characteristic
Rated output current (rms)
Maximum output current (peak)
Inverter overload capacity
Environment
External dimensions (1.2 KVA)
External dimensions (1.5 - 2 KVA)
Switches
Interfaces
Fault detect and input power loss
Options
Software for unattended
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.
MODEL NUMBER
UC1A1A012C6B
CAPACITY
1200 VA (0.84 kW)
Input voltage
Single phase, 120 Vac, +10% to -30% (*)
Input frequency
45 to 65 Hz
Input capacity
Input power factor
Approximate unity (0.98 to 1.0)
Battery rated voltage
10 min. at full load (**) 10 min. at full load (**)
30 min. at half load (**) 30 min. at half load (**) 30 min. at half load (**)
Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed lead-acid
Output voltage
Single-phase, 120 volts
Within +/- 3%, steady state
Output frequency
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
0.7 lagging (0.6 to 1.0)
+/- 5% under 100% load step change
150% for 60 seconds
Crest factor
3.0
Operating temperature
32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature
-4 to 104° F (-20 to 40° C)
Operating humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
7.06W x 20.44D x 14.63H in (179W x 519D x 371H mm)
7.06W x 23.16D x 14.63H in (179W x 588D x 371H mm)
Net weight
76 lb (34.5 kg)
Acoustical noise
45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
Bypass switch
Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
IBM (TM) AS/400
Pins 5 through 9
LAN Manager
Pins 2 and 3
Pins 1 and 4
RS232 ASCII
Pins 1 through 8
computer shutdown
Contact Toshiba for details on this option
External battery pack
Contact Toshiba for details on this option
UC1A1A015C6B
1500 VA (1.05 kW)
1200 VA
1500 VA
48 Vdc
72 Vdc
10.0A
12.5A
30.0A
37.5A
96 lb (43.6 kg)
87%
87%
DB9 male connector
DB9 female connector (Pin 9 not used)
4 - 2
UC1A1A020C6B
2000 VA (1.4 kW)
1920 VA
96 Vdc
10 min. at full load (**)
16.7A
50.0A
106 lb (48.2 kg)
87%

Hide quick links: