BYTE 0:
Bit 7 - Not used
Bit 6 - Not used
Bit 5 - If OL is set to 1, the stall prevention is activated.
Bit 5 - If OL is set to 0, the stall prevention is not activated.
Bit 4 - If FU is set to 1, the output frequency is above the set value.
Bit 4 - If FU is set to 0, the output frequency is less the set value.
Bit 3 - Not used
Bit 2 - Faulted - An error has occurred with the inverter.
Bit 1 - Reverse run
Bit 0 - Forward run
BYTE 1: 00
BYTE 2: Low-order byte of actual speed (speed).
BYTE 3: High-order byte of actual speed (speed).
BYTE 4: Low-order byte of output current.
BYTE 5: High-order byte of output current.
BYTE 6: Error cause code when inverter alarm occurs. (Refer to alarm code table provided later.)
BYTE 7: 00
40
OBJECT MAP