Output From Inverter To Devicenet 21 - Mitsubishi Electric DeviceNet FR-E5ND Instruction Manual

Transistorized inverter, option
Table of Contents

Advertisement

4.5 Output from Inverter to DeviceNet
4.5.1 Inverter Status
Inverter status can be monitored using class 0x2A, attribute 114, the FR-E520S/FR-E540 inverter status. This is a bit-
mapped status byte defined as follows:
4.5.2 Inverter Monitoring
The following items can be monitored:
O utput frequency
-
O utput current
-
O utput voltage
-
Bit
0
Running
1
Forward running
2
Reverse running
3
Up to frequency
4
Overload
5
-
6
Frequency detection
7
Alarm
Definition
(RUN)
(FWD)
(REV)
(SU)
(OL)
(FU)
21
OPERATION
-
-

Advertisement

Table of Contents
loading