BYTE 0:
Bit 7 - If Write parameter = 1, the Parameter Write Data is written to the parameter and the rest of the parameter is
ignored.
Bit 7 - If Write Parameter = 0, the Speed Ref in RPM is set, and the rest of the command byte is executed.
Bit 6 - If NetRef = 1, the Speed Ref is taken from BYTE 2 and BYTE 3.
Bit 5 - If NetControl = 0, the Speed Ref from the result of the AC Drive parameter settings.
Bit 4 - Not Used.
Bit 3 - Not Used.
Bit 2 - If Fault Reset makes a transition from 0 to 1 and there is an error in the inverter, the inverter will reset.
Bit 1 - If Run Rev = 1 and Run Fwd = 0, the drives rotates in the reverse direction.
Bit 0 - If Run Fwd = 1 and Run Rev = 0, the drives spins in the forward direction.
Note: Net Control must = 1 for Bits 2, 1, 0 to have any affect.
BYTE 1: Must be Zero (00).
BYTE 2: Low Byte of the Speed Ref or Data Value.
BYTE 3: High Byte of the Speed Ref or Data Value.
BYTE 4: Parameter Class, e.g. 0x2A, 0x66, 0x67.
BYTE 5: Parameter Attribute Number, e.g. 0x0A, 0x65.
33