GETTING STARTED
When the EPR bits of Pr. 345 and Pr. 347 are set to decimal 0, the inverter will continue to execute the last command
received until the communication time-out is reached. This time out value is equal to 4 times the Expected Packet Rate
(EPR) as configured by the user (this is set in the master controller). Once the FR-E5ND times out, the inverter will generate
an E.OPT error and coast (free-run) to a stop.
When the EPR bits of Pr. 345 and Pr. 347 are set to decimal 2, the inverter will continue to execute the last command
received until another command is issued. The FR-E5ND will ignore the communication loss, generate no error and
automatically reset the connection when communication is restored.