Mitsubishi Electric DeviceNet FR-E5ND Instruction Manual page 44

Transistorized inverter, option
Table of Contents

Advertisement

BYTE 0:
Bit7 - If Write Parm is set to 1, the acceleration/deceleration time value will be written into the parameter.
(The write conditions follow Pr. 77.)
Bit7 - If Write Parm is set to 0, the acceleration/deceleration time value will not be written into the parameter.
Bit6 - If NetRef is set to 1, the speed setting value will be incorporated from BYTE2 and BYTE3.
Bit6 - If NetRef is set to 0, the speed setting value will be the value set from the parameter unit.
Bit5 - If NetCtrl is set to 1, MRS, FaultReset, reverse run and forward run can be operated with communication.
Bit5 - If NetCtrl is set to 0, MRS, FaultReset, reverse run and forward run can be operated with the inverter unit's
external terminals.
Bit4 - Not used
Bit3 - If MRS is set to 1, the inverter output will be shut off.
Bit3 - If MRS is set to 0, the inverter will cancel the shut off output.
(MRS can be assigned with Pr. 183.)
Bit2 - If FaultReset is changed from 0 to 1, and there is an error in the inverter, the inverter will reset.
Bit1 - If Reverse run is set to 1 and forward run to 0, the motor will reverse run.
Bit0 - If Forward run is set to 1 and reverse run to 0, the motor will forward run.
Note: NetCtrl must be set to 1 to validate Bit3, 2, 1 and 0.
BYTE 1: Must be 00.
BYTE 2: Low-order byte of speed setting value (speed).
BYTE 3: High-order byte of speed setting value (speed).
BYTE 4: Low-order byte of acceleration time.
BYTE 5: High-order byte of acceleration time.
BYTE 6: Low-order byte of deceleration time.
BYTE 7: High-order byte of deceleration time.
35
OBJECT MAP