Ci600 Advanced User Menu; Pin; Advanced User; Temperature Regulation - Flexit K2.1 User Manual

Air handling unit with kitchen hood and control automation
Hide thumbs Also See for K2.1:
Table of Contents

Advertisement

8.

CI600 advanced user menu

INFO! For more information on the
"Advanced User" menu, refer to
i
the "CI600 Reference Manual" on
Flexit's homepage.

8.1. PIN

To access the menu item, you need to enter the PIN 1 0 0 0.
PIN CODE
1 0 0 0

8.2. ADVANCED USER

This menu contains functions for monitoring,
do with adjustment can be found in the installation
instructions. Complete documentation of all menus,
is described in the CI600 reference manual, which is
ADVANCED USER

TEMPERATURE REGULATION

FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
8.3. TEMPERATURE REGULATION
regulation and cooling functions.
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
K 2 . 1
OK?
>
OK?
>
>
>
>
>
>
OK?
>
Regulation type
If supply air regulation is selected, no further settings
can be set here. If extract air regulation is selected,
the max. and min. supply air temperatures can also be
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
Cooling
INFO! Flexit does not supply or
project cooling machines.
i
In this dialog, the cooling function is activated and
the parameters MIN OUTDOOR AIR TEMP for supply
of cooling and MIN SPEED for supply of cooling are
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
It is also possible to activate a function to recover cooling
in the building using the rotating heat exchanger. Enter
air temperatures for when the function is activated.
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
19
EXTR OK?
35°
15°
AV
OK?
18°
MIN
180 s
>
OFF
OK?