Mounting
2.1

Mount the sensor

Use your common practices to minimize torque and bending load on process connections.
About this task
Tip
To reduce the risk of condensation problems, do not orient transmitters or sensor junction
boxes with their conduit openings pointing upward.
Do not lift the sensor by the electronics or purge connections. Lifting the sensor by
the electronics or purge connections can damage the device.
Figure 2-1: Mounting the sensor
Notes
Do not use the sensor to support the piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation.
Installation Manual
CAUTION
Mounting
January 2019
9