9.2 Error Message & Trouble Shooting
Message
E01: Grid Freq.
Over Rating
E02: Grid Freq.
Under Rating
E07:Grid Quality
E09: No Grid
E10: Grid Volt
Under Rating
E11: Grid Volt
Over Rating
E13: Slow Over
Voltage Range
E26:Slow Over
Frequency Range
Possible cause
1. Actual utility frequency is over
the OFR setting
2. Incorrect country setting
3. Detection circuit malfunction
1. Actual utility frequency is
under the UFR setting
2. Incorrect country or Grid setting
3. Detection circuit malfunction
Non-linear load in Grid and near
to inverter
1. AC breaker is OFF
2. Disconnect in AC plug
3. Internal fuses are broken
1. Actual utility voltage is under the
UVR setting
2. Utility voltage is under the Slow
UVR setting during operation
3. Incorrect country or Grid setting
4. Detection circuit malfunction
1. Actual utility voltage is over the
OVR setting
2. Utility voltage is over the Slow
OVR setting during operation
3. Incorrect country or Grid setting
4. Detection circuit malfunction
1. Actual utility voltage is over the
OVR setting
2. Incorrect country or Grid setting
3. Detection circuit malfunction
1. Actual utility frequency is over
the OFR setting
2. Incorrect country or grid setting
3. Detection circuit malfunction
Measurement, Error Message and Trouble Shooting
ERROR
1. Check the utility frequency on
the inverter terminal
2. Check country setting
3. Check the detection circuit inside
the inverter
1. Check the utility frequency on the
inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside
the inverter
Grid connection of inverter need to
be far away from non-linear load
if necessary
1. Switch on AC breaker
2. Check the connection in AC plug
and make sure it connects to
inverter
3. Replace fuses and check all
switching devices in boost &
inverter stages
1.&2. Check the utility voltage
3. Check country & Grid setting
4. Check the detection circuit inside
the inverter
1.&2. Check the utility voltage on
3. Check country & Grid setting
4. Check the detection circuit
inside the inverter
1. Check the utility voltage on the
inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside
the inverter
1. Check the utility frequency on
the inverter terminal
2. Check country setting
3. Check the detection circuit inside
the inverter
47
Action
connection to the inverter
terminal.
the inverter terminal