4. Default Settings

Default setting for I-7012/12D/12F/12FD/14D/17/17F :
z Address : 01
z Analog Input Type : Type 08, -10 to +10 V
z Baudrate : 9600 bps
z 60Hz filter rejection, Checksum disable, engineer unit format
z I-7017/17F set as 6 differential and 2 single-ended mode
z I-7012F and I-7017F set as Fast Mode
5. Configuration
To install the module, follow the steps below:
1. Connect the analog output.
2. Connect the module to the RS-485 network using the DATA+ and DATA- terminals. If
the host is only equipped with an RS-232 interface, then an RS-232 to RS-485
converter will be required.
3. Connect the module to the power supply using the +Vs and GND terminals. Note that
the voltage supplied should be in the range of +10 to +30V DC.
I-7014D AI DAQ Module - QuickStart (Jan/2017)
ICP DAS USA, Inc. |
www.icpdas-usa.com
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717