Default Settings - ICP DAS USA I-7041 Quick Start Manual

14 channel isolated digital input data acquisition module

Advertisement

4. Default Settings

Default settings for the I-7043 DIO modules are as follows:
。 Module Address: 01
。 DIO Type: Type 40
。 Baud Rate: 9600 bps
。 Checksum disabled
。 J3 set to INIT mode enabled for I-7043/43D a
5. Configuration
To install the module, follow the steps below:
1. Connect the analog output.
2. Connect the module to the RS-485 network using the DATA+ and DATA- terminals. If
the host is only equipped with an RS-232 interface, then an RS-232 to RS-485
converter will be required.
3. Connect the module to the power supply using the +Vs and GND terminals. Note that
the voltage supplied should be in the range of +10 to +30V DC.
I-7041
14 Ch DI DAQ Module- QuickStart (Jun/2018)
ICP DAS USA, Inc. |
www.icpdas-usa.com
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
3