Connection of EMM to Line Voltage

(Not on Gateway-on-the-Go, IE Express, or
WMC kits)
The EMM is connected to Line Voltage through the Fuse
Block. Begin by removing the fuse covers and fuses from the
Fuse Block. Prior to removal, make note of fuse orientation
within the fuse block. Next, using the provided 6" wiring
harness, connect the "VinA" (Tan), "VinB" (Orange), and
"VinC" (Violet) terminals on the EMM to the "Load" terminals
on the Fuse Block
(Figure
33).
If needed, remove the plastic protective shield from Power
Distribution Block 1 (PD1).Using the provided 6' wiring
harness, connect the corresponding "Line" terminals on the
Fuse Block to the control panel (PD1) terminals "T1", "T2",
and "T3", such that EMM terminal "VinA" (Tan) is connected to
PD1-T1, "VinB"(Orange) is connected to PD1-T2, and "VinC"
(Violet) is connected to PD1-T3
www.DaikinApplied.com
(Figure
34).
Figure 33: EMM Connection to Fuse Block
Figure 34: Fuse Block Connected to Line Voltage
PD1
FUSE BLOCK
17
Installation
IM 1240-4 • INTELLIGENT EQUIPMENT