Chapter 3
Installing a Cisco MGX 8950
Place the air intake plenum on a flat and stable surface (for example, a table top) and use mounting
Step 1
screws and a Phillips-head screwdriver to attach the front-mounting brackets to the sides of the air intake
plenum if you are installing the system in a 23-inch rack.
Step 2
Place the air intake plenum on a flat and stable surface (for example, a table top) and use mounting
screws and a Phillips-head screwdriver to attach the mid-mounting brackets to the air intake plenum if
you are installing the system in a 19-inch rack.
Position the air intake plenum, which occupies 3 RUs of space, either at the bottom of the configuration
Step 3
or rack (for a DC-powered system) or directly above the AC power supply tray (for an AC-powered
system).
Use four mounting screws and a Phillips-head screwdriver to bolt the air intake plenum in the rack. See
Step 4
Figure 3-4
Install the Lower Fan Tray
Complete the following steps to install the lower fan tray:
If a component requires more than two screws to install it in the rack or cabinet, install the two bottom
Tip
screws first.
Place the lower fan tray on a flat and stable surface (for example, a table top) and use mounting screws
Step 1
and a Phillips-head screwdriver to attach the front-mounting brackets to the lower fan tray if you are
installing the system in a 23-inch rack.
Step 2
Place the lower fan tray on a flat and stable surface (for example, a table top) and use mounting screws
and a Phillips-head screwdriver to attach the mid-mounting brackets to the lower fan tray if you are
installing the system in a 19-inch rack.
Position the lower fan tray, which occupies 1 RU of space, directly above the air intake plenum.
Step 3
Ensure that the air flow direction arrow on the back of the lower fan tray is pointing up, as shown in
Figure
Figure 3-10 Lower Fan Tray Air Flow Direction
Use four mounting screws and a Phillips-head screwdriver to bolt the lower fan tray in the rack. See
Step 4
Figure 3-4
Release 3, Part Number 78-14147-02 Rev. A0, November 2002
for the correct placement of the air intake plenum.
3-10.
UP
AIR FLO W
DIRE CTIO N
for the correct placement of the lower fan tray.
Cisco MGX 8950 Hardware Installation Guide
Installation Procedures
3-19