Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: Unavailable models are A6T6 with 2A0002, A6T15 with 2A0004 or
4A0004, A6T20 with 4A0005, and A6T25 with 4A0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Non-Time Delay
Model
Class-T Fuse Type
CIMR-VC
(Manufacturer: Ferraz)
600 Vac, 200 kAIR
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
BA0018
2A0001
2A0002
2A0004
2A0006
2A0010
2A0012
2A0020
2A0030
2A0040
2A0056
2A0069
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
EN 12
Single-Phase 200 V Class
A6T6
A6T10
A6T20
A6T40
A6T40
A6T50
A6T80
Three-Phase 200 V Class
A6T3
A6T6
A6T15
A6T20
A6T25
A6T30
A6T40
Not Available
Three-Phase 400 V Class
A6T3
A6T6
A6T15
A6T20
A6T25
A6T25
A6T30
YASKAWA Europe TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
Fuse Ampere
Rating (A)
500 Vac, 200 kAIR
6
10
20
40
40
50
80
3
6
15
20
25
30
40
3
6
15
20
25
25
30
Fuse Type
(Manufacturer:
Bussmann)
FWH-25A14F
FWH-25A14F
FWH-60B
FWH-80B
FWH-100B
FWH-125B
FWH-175B
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-70B
FWH-70B
FWH-90B
FWH-100B
FWH-200B
FWH-200B
FWH-200B
FWH-40B
FWH-40B
FWH-50B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
Fuse Ampere
Rating (A)
25
25
60
80
100
125
175
25
25
25
25
70
70
90
100
200
200
200
40
40
50
70
70
90
90

Hide quick links: