TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B
Parameter descriptions
DTM menu path, parameters
<Device> / <Extras>
<Write Protection>
<Device reset>
<Factory reset>
<Device> / <Configuration>
<Sensor / Sensor type>
<Sensor / Connection>
<Sensor / Line resistance>
Description
Activates write protection for the entire device
•
Yes: locked, entry combination: ≠ 0110
•
No: unlocked, entry combination: 0110
Configuration data is reset to factory settings
(see Factory settings on page 29).
Configuration data is reset to factory settings
(see Factory settings on page 29).
In addition, the adjustment data and DAC adjustment values are also reset to factory settings.
•
Yes / OK
Selects sensor type:
•
Pt100 (IEC751)
•
Pt1000 (IEC751)
•
Thermocouple type K (IEC584)
•
Thermocouple type B (IEC584)
•
Thermocouple type C (ASTME988)
•
Thermocouple type D (ASTME988)
•
Thermocouple type E (IEC584)
•
Thermocouple type J (IEC584)
•
Thermocouple type N (IEC584)
•
Thermocouple type R (IEC584)
•
Thermocouple type S (IEC584)
•
Thermocouple type T (IEC584)
•
Thermocouple type L (DIN43710)
•
Thermocouple type U (DIN43710)
•
Thermal voltage -125 to 125 mV
•
Thermal voltage -125 to 1100 mV
•
Resistance 0 to 500 Ω
•
Resistance 0 to 5000 Ω
Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers
•
Two-wire: sensor connection type in two-wire technology
•
Three-wire: sensor connection type in three-wire technology
•
Four-wire: sensor connection type in four-wire technology
Sensor line resistance relevant for all Pt, Ni, Cu resistance thermometers with a two-wire circuit
Value range: 0 to 100 Ω
•
Pt10 (IEC751)
•
Pt50 (IEC751)
•
Pt200 (IEC751)
•
Pt500 (IEC751)
•
Pt10 (JIS1604)
•
Pt50 (JIS1604)
•
Pt100 (JIS1604)
•
Pt200 (JIS1604)
•
Pt10 (IMIL24388)
•
Pt50 (IMIL24388)
•
Pt100 (MIL24388)
•
Pt200 (MIL24388)
•
Pt1000 (MIL24388)
•
Ni50 (DIN43760)
•
Ni100 (DIN43760)
•
Ni120 (DIN43760)
•
Ni1000 (DIN43760)
•
Cu10 (OIML R 84), a=4270
•
Cu100 (OIML R 84), a=4270
27