TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B

Input - thermocouples / voltages

Types
B, E, J, K, N, R, S, T in accordance with IEC 60584
U, L in accordance with DIN 43710
C, D in accordance with ASTM E-988
Voltages
−125 to 125 mV
−125 to 1100 mV
Connection lead
Maximum sensor line resistance:
per line 1.5 kΩ, total 3 kΩ
Sensor wire break monitoring in accordance with NE 89
Pulsed with 1 µA outside measurement interval
Thermocouple measurement 5.3 to 10 kΩ
Voltage measurement 5.3 to 10 kΩ
Input resistance
> 10 MΩ
Internal reference junction Pt1000, IEC 60751 Cl. B
(no additional jumpers necessary)
Sensor error signaling
Thermocouple:
Sensor wire break
Linear voltage measurement:
Sensor wire break

Output

Note
The HART protocol is not secure, as such the intended
application should be assessed to ensure that these protocols
are suitable before implementation.
Transmission characteristics
Temperature linear
Resistance linear
Voltage linear
Output signal
Configurable 4 to 20 mA (standard)
Configurable 20 to 4 mA
(Dynamic range: 3.8 to 20.5 mA in accordance with NE 43)
Simulation mode
3.5 to 23.6 mA
Induced current consumption
< 3.5 mA
Maximum output current
23.6 mA
Configurable error current signal
Overrange 22 mA (20.0 to 23.6 mA)
Underrange 3.6 mA (3.5 to 4.0 mA)