8 Commissioning

General

In case of corresponding order the transmitter is ready for
operation after mounting and installation of the connections.
The parameters are set at the factory.
The connected lines must be checked for firm seating. Only
firmly seated lines ensure full functionality.

Checks prior to commissioning

The following points must be checked before commissioning the
device:
Correct wiring in accordance with Electrical connections
on page 17.
The ambient conditions must correspond to the
information given on the name plate and in the data
sheet.

Communication

Note
The HART protocol is not secure, as such the intended
application should be assessed to ensure that these protocols
are suitable before implementation.
Communication with the transmitter takes place using the HART
protocol. The communication signal is modulated onto both
wires of the signal line in accordance with the HART FSK 'Physical
Layer' specification.
The HART modem is connected at the signal line of the current
output via which power is also supplied via the power supply
unit.
The device is listed with the FieldComm Group.
1 Transmitter
2 Handheld terminal
3 HART® modem
4 PC with Asset Management Tool
Figure 24: Example for HART connection
Manufacturer ID
Device Type ID
Profile
Configuration
Transmission signal
Operating modes
Point-to-point communication mode –
standard (general address 0)
Multidrop mode (addressing 1 to 15)
Burst Mode
Diagnosis notice
Overrange / underrange in accordance with NE 43
HART® diagnosis
5 Grounding (optional)
6 Power supply unit
(process interface)
R
load resistance
B
(if necessary)
HART® 5.1
DTM, EDD, FDI (FIM)
BELL Standard 202