ABB TTF200 Operating Instructions Manual page 28

Field-mount temperature transmitter. temperature transmitter for hart protocol. suitable for all standard requirements
Hide thumbs Also See for TTF200:
Table of Contents

Advertisement

28
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B
... 8 Commissioning
... Parameterization of the device
DTM menu path, parameters
<Device> / <Configuration>
<Sensor / Reference junction>
<Sensor / Reference junction
temperature>
<Device > / <Parameterize>
<Measuring range of PV / unit>
<Measuring range of PV / lower range
value>
<Measuring range of PV / upper range
value>
<Current output / damping>
<Current output / output upon error >
(overrange)
<Current output / output upon error >
(underrange)
<Device> / <Maintenance>
<Poll address / TAG> (HART TAG)
<Poll address / TAG>
(Address (Multidrop))
<Adjustment> (Set lower range value) Temperature correction for specified / simulated sensor lower range value to target lower range temperature value
<Adjustment /DAC adjustment fixed
for zero at 4 mA>
<Adjustment /DAC adjustment fixed
for amplification at 20 mA>
<Device> <Simulation>
Description
Internal: use of the internal reference junction of the transmitter when using a thermocouple / compensating cable
(relevant for all thermocouples except for type B)
External - fixed: transfer of thermal cable / compensating cable via copper material at constant thermostat
temperature
Without: no reference junction
Relevant for external reference junction, specification of constant external reference junction temperature
Value range: −50 to 100 °C
Selects the physical unit for the sensor measuring signal
Units: °C, °F, °R, K, mV, Ω, mA
Defines the value for 4 mA (adjustable)
Defines the value for 20 mA (adjustable)
Configurable τ 63% output signal damping value
Value range: 0 to 100 s
Generates a high alarm signal in the event of a sensor or device error; can be configured 20 to 23.6 mA
Standard 22 mA
Generates a low alarm signal in the event of a sensor or device error; can be configured 3.5 to 4 mA
Defines the HART TAG name.
8 characters, alphanumeric
Specifies the communication type
Address = 0 conforms to HART operating mode: point-to-point communication, 4 to 20 mA output signal
Address = 1 to 15 conforms to HART multidrop operating mode output signal 3.6 mA, only the digital HART measured
values are available
Set Trim low or lower range value > OK
Output signal correction for specified / simulated sensor LRV value to 4.000 mA set point
Analog current measurement value input 3.5 to 4.5 mA
Output signal correction for specified / simulated sensor URV value to 20.000 mA set point
Analog current measurement value input 19.5 to 20.5 mA
Output signal simulation corresponding to the value specified
Value range: 3.5 to 23.6 mA

Advertisement

Table of Contents
loading

Table of Contents