Advertisement

TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B
Possible error messages – HART®
Range
device status
Electronics
Electronics
Electronics
Electronics
Electronics
Electronics
Installation / Configuration
Electronics
Electronics
Electronics
Electronics
Installation / Configuration
Sensor
Sensor
Sensor
Sensor
Sensor
Installation / Configuration
Installation / Configuration
Installation / Configuration
Installation / Configuration
Operating conditions
Installation / Configuration
Installation / Configuration
Operating conditions
Note
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
Change from one to two columns
Displays the
Displays the
Cause
DIAG. NO.
F
1
Device defective
S
2 Ambient temperature overshot / undershot
F
3
EEPROM defective
M
4 Electronics overload
F
5 Memory error
I
7 LCD indicator connected
I
8 Device write-protected
I
9
EEPROM busy
F
12
Sensor input defective (communication)
F
13 Sensor input defective (error)
F
14 Sensor input defective (ADC error)
C
32 Diagnostics simulation mode
F
34
Measuring error, sensor
F
35 Short-circuit, sensor
F
36
Wire break, sensor
F
37
Range overshot, sensor
F
38
Range undershot, sensor
I
41
Single-point adjustment active, sensor
I
42
Two-point adjustment active, sensor
F
65 Configuration defective
C
71
Reconfiguration is running
F
72
Error in the application
I
74
Analog output adjustment active
C
75
Analog output in simulation
S
76
Values overshot
Remedy
Replace the device
Check environment; reposition measuring point
if required
Replace the device
Factory reset
Factory reset
Status info; not an error
Status info; not an error
Status info; not an error
Replace the device
Replace the device
Replace the device
Not an error, diagnostic info, measurement OK
Check sensor connection
Check sensor connection
Check sensor connection
Check measuring limits
Check measuring limits
Status info; not an error
Status info; not an error
Check configuration:
Incorrect device
Measuring span is too small
Incorrect configuration data
Status info; not an error
Check configuration, connections; reset to
factory settings
Status info; not an error
Status info; not an error
Check parameters:
Sensor limits up-scaled
Measuring span is too small