Wolf WRS-K Installation And Operating Instructions Manual page 41

Regulatory system
Table of Contents

Advertisement

3062878_201707
10. Operating level 2
Parameter
Control type
Set value deviation, offset,
heating
Set value deviation, offset,
cooling
Interlock between
heating / cooling
Enable acc. to outside
temperature
Offset heating
Offset cooling
Temp. diff. for natural cooling
Speed reduction enabling
Delay
Outside temperature BMS
enable
Setting range
Room-vent. air
cascade/Extract
air-vent. air cascade/
Vent. air control
0 - 20 K
0 - 20 K
0 - 99 min
Yes/No
-20 – 20 K
-20 – 20 K
1 - 20 K
Yes/No
0 - 30 min.
Yes / No
Factory setting
Subject to order
0 K
2 K
0 min
No
5 K
5 K
2 K
Yes
5 min.
No
41