10.2.10 Compensation
(condition: outside and room
temperature sensor installed)
SP compensation
Summer:
START at:
END at:
Esc BACK
SELECTION
3062878_201707
10. Operating level 2
Standard mask
Compensation
Summer compensation:
SW-01
In cooling mode, the set room temperature is adjusted subject to outside
0.0 K
temperature. In other words, at high outside temperatures, the room temperature
is raised in accordance with these parameters. This prevents excessively high
24.0 °C
temperature differentials between the room temperature and the outside temperature.
In addition, this reduces the energy expended on cooling.
36.0 °C
Set room
DISPLAY
temperature
Selected
set value
Winter compensation
In heating mode, the set room temperature is adjusted subject to outside
temperature. This increases the set room temperature when outside temperatures
are very low.
Set room
temperature
Selected
set value
Please note In "Summer" or "Winter" = 0 this function is disabled
Parameter
Summer
Start at outside temperature
End at outside temperature
Winter
Start at outside temperature
End at outside temperature
Main menu
Esc
Maximum
compensation
Start temperature
End temperature
(no compensation).
Setting range
0 - 4 K
2 - 42 °C
2 - 42 °C
0 - 4 K
-15 - 15 °C
-15 - 15 °C
Heating contractor
Outside temperature
End temperature
Maximum
compensation
Outside temperature
Start temperature
Factory setting
0 K
24 °C
36 °C
0 K
5 °C
-15 °C
39