10.2.5 Limits

Limits
Set value limits
maximum
minimum
Esc BACK
SELECTION

10.2.6 Heat generation

(condition: outside temperature
sensor present)
Heat generation
Enable preheat program
Esc BACK
SELECTION
32
10. Operating level 2
Standard mask
Limits
GW-01
Limits can be defined for the temperature and speed of the air handling
28.0 °C
system via the following parameters.
16.0 °C
Parameter
DISPLAY
Set value limits, maximum
Set value limits, minimum
Ventilation air limit maximum temperature
Ventilation air limit minimum temperature
Min. speed, ventilation fan
Max. speed, ventilation fan
Min. speed, extract fan
Max. speed, extract fan
*
in systems without room set value transducer
** in systems with room set value transducer
*** for systems with stepped or stepless electric heater bank
Standard mask
Heat generation
Preheat program
VW-01
The preheat program can be activated via a parameter.
Activating the preheat program prevents cold air being blown into the room
at system start (when heating coil (bank) is cool).
Prior to the fan starting, the system checks whether the outside temperature
Yes
lies below an adjustable limit. If that is the case, the heating circuit pump
starts for a programmed time, and the valve opens.
DISPLAY
The preheat program cannot be activated on systems with an electric
heating coil.
KGWO
The parameters ensure that when the KGWO is active, there is always
a minimum air flow across the heat exchanger. When the contact of the
thermostat for fan run-on closes, the air damper is opened to the set
minimum damper position.
Main menu
Esc
Setting range
14-20 °C* / 10 °C**
Main menu
Esc
Heating contractor
Factory setting
22 - 70 °C
28 °C*/29 °C**
16 °C*/10 °C**
22-70 °C
42 °C
14-20 °C
16 °C*/10 °C**
1 - 100 %
25 % / 35 % ***
1 - 100 %
100 %
1 - 100 %
25 % / 35 % ***
1 - 100 %
100 %
Heating contractor
3062878_201707