Chapter 10 Protective Functions
Overload trip
Group
Code
Function
F56
group 1
F57
F58
 Set F56 to 1 in the function group 1
Inverter output is turned off when motor is overloaded.
Inverter output is turned off when motor current reaches to over trip level
(F57) for overload trip time (F58).

10.3 Stall prevention

Group
Code Parameter
Function
F59
group 1
F60
I/O Group
I55
 During acceleration: Motor starts deceleration when current exceeding the
value set in F60 flows.
During constant run: Motor decelerates when current exceeding the value
set in F60.
 During deceleration: Motor deceleration is stopped when inverter DC link
voltage rises above a certain voltage level.
F60: The value is set as the percent of motor rated current (H33).
 I55: Multi-function relay can transmit the stall status to the parts outside.
The output can be achieved if the motor is connected though F59 is not
selected for stall prevention.
10-3
Parameter
Overload trip select
Overload trip level
Overload trip time
Stall prevention select
Stall prevention level
Multi-function relay
function select
Set Value
Range
1
0 ~ 1
-
30 ~ 200 180
-
0.0~ 60.0 60.0
Set Value
Range
-
0 ~ 7
-
30 ~ 200
7
0 ~ 19
Initial
Unit
1
%
sec
Initial
Unit
0
150
%
17