9 Monitoring

9.1 Operating status monitoring

Output current
Group
Code
Drive group
CUr
Inverter output current can be monitored in Cur.
Motor RPM
Group
Drive group
Function group 2
Motor rpm can be monitored in rPM,. This rpm is the synchronous one imposed on the motor.
When H40 is set to 0 (V/F control), the Inverter output frequency (f) is displayed in rPM using the formula
below. Motor slip is not considered.
In case that H49 code is 1 (PID control), Feed back amount is converted into frequency.
H31: Enter the number of rated motor poles on the nameplate.
H74: This parameter is used to change the motor speed display to mechanical speed.
Inverter DC Link Voltage
Group
Drive group
Inverter DC link voltage can be monitored in dCL.
times the value of input voltage is displayed while motor is at a stop.
2
Cx2000 AC Drive
Name
Output current
Code
Name
rPM
Motor RPM
H31
Number of motor poles
H49
PID control select
H74
Gain for Motor rpm display -
120
f
RPM
H
31
Code
Name
dCL
Inverter DC Link Voltage
Set Value
Range
-
Set Value
Range
-
-
2 ~ 12
-
0 ~ 1
1 ~ 1000
H
74
100
Set Value
Range
-

Chapter 9 Monitoring

Default
Unit
Default Unit
4
0
100
%
Default
Unit
9-1