Chapter 8 Application
0: continuous operation when cooling fan trip occurs.
-. Operation is not stopped regardless of cooling fan trip.
-.When I55 is set to 18 (cooling fan fault alarm), fault alarm signal can be output using Multi-function
relay.
If operation is continued after cooling fan trip occurs, Overheat trip may happen and
protective function be activated. It also reduces the life of main components due to rise in
inverter inner temperature.
1: operation stopped at cooling fan fault
-.when cooling fan fault occurs,
stopped.
-. If I55 is set to 17(Fault output), fault message is displayed.
8.24 Input voltage set of inverter
Group
Code
Function Group 1
F67
Function Group 1
F68
F67 set input voltage of 230V level inverter
F68 set input voltage of 415V level inverter
The adjustment of input voltage will influence the voltage level when failure of inverter occurs under low
voltage

8.25 Parameter Initialize / Lock

Parameter initialize
Group
Function group 2
Select the group to be initialized and perform it in H93 code.
8-30
Caution
message is displayed on the LED and operation is
Item
Input voltage for 230V inverter
Input voltage for 415V inverter
Code Item
H93
Parameter initialize
Set
Setting
Value
Range
170~240
320~480
Setting Range
0
-
1
All groups initialize
2
Drive group initialize
3
Function group 1 initialize
4
Function group 2 initialize
5
I/O group initialize
Initial
Unit
220
380
Initial
0
Cx2000 AC Drive