Energy-Saving Operation - Larsen & Toubro C*2000 Series User Manual

Variable frequency drive 0.1-11kw (230v, 415v)
Table of Contents

Advertisement

8.10 Energy-saving operation

Group
Function Group 1
Set the amount of output voltage to be reduced in F40.
Set as the percent of Max output voltage.
For fan or pump applications, energy consumption can be dramatically reduced by decreasing
the output voltage when light or no load is connected.
Output
current
Output
voltage
8.11 Speed search
Group
Function group 2
I/O Group
 This is used to prevent possible fault from occurring if the inverter outputs the voltage during
operation after the load is removed.
 The inverter estimates the motor rpm based on output current. Therefore, detecting exact
speed is difficult.
Cx2000 AC Drive
Code Item
F40
Energy-saving level]
전 류
출 력 전 압
Code Item
H22
Speed search select
H23
Current level
H24
Speed search P gain
H25
Speed search I gain
I55
Multi-function relay select]
Chapter 8 Application
Set Value
Setting Range
0 ~ 30
-
F 4 0
Set Value
Setting Range Initial
0 ~ 15
-
-
80 ~ 200
-
0 ~ 9999
-
15
0 ~ 19
Initial
Unit
%
0
Unit
0
150
%
100
200
17
8-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents