Electrical Supply Installation; (Usa 3Ph, 200 - 240V) - Seeley Climate Wizard CW-H10 Installation & Operation Manual

Indirect evaporative cooler
Hide thumbs Also See for Climate Wizard CW-H10:
Table of Contents

Advertisement

INSTALLATION cont.

ELECTRICAL SUPPLY INSTALLATION

(USA 3PH, 200 - 240V)

CW-H15, CW-H15S ONLY
Please Note! There are specific models for regional specific
voltages and frequencies which are not interchangeable,
as these require differing component configurations that vary
according to the supply frequency and voltage. Specifically, the
main fan motor, 3 phase filter, transformer and pump are unique
to the voltage/frequency of supply.
INSTALLATION OF THE COOLER MUST CONFORM
TO LOCAL ELECTRICAL CODES, REGULATIONS AND
STANDARDS.
It is a requirement of Seeley International that all Coolers
be wired with a dedicated circuit and circuit breaker to the
distribution board, incorporating an isolation switch in the fixed
wiring with all pole disconnection from the mains power in
accordance with the National Electric Code.
Specification : 200 - 240V / 60Hz / 3 Phase / 6 Amps per
phase, 14.5 MCA, 20 MOPD*
Climate Wizard requires 3-phase (No Neutral) and Ground
electrical power. If required, mains isolation switch is to be
furnished by the contractor adjacent to the cooler - if mounting
on the cooler cabinet, take care not to puncture the water
reservoir. Mains power terminals are provided inside the
electrical cabinet with glands provided for cable entry.
CW-H15 Models
230Vac
INPUT
CLASS 2
POWER SUPPLY
12Vdc
MPS-30-12
OUTPUT
MAIN PCB
C11
C8 C9 C10
C7
C2
C6
C1
C3
C4
C5
PUMP JUNCTION BOX
1
3
5
A1
gn/y
T1 T2 T3 T4 T5 T6 T7
2
4
6 A2
L1
L2
FAN
MAIN SUPPLY
CW-H15S, H15S Plus Models
230Vac
INPUT
CLASS 2
POWER SUPPLY
12Vdc
C1 MOTOR CONTACTOR COIL
MPS-30-12
OUTPUT
MAIN PCB
C2 FUSE T12.5A
DENOTES CLASS
C3 MAIN PCB POWER IN
2 CIRCUIT
C4 PUMP LINK
C11
C5 DRAIN VALVE
CHLORINATOR
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C8 C9 C10
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C7
C2
C11 INTERFACE BOARD LINK
C6
C12 NOT USED
C4
C1
C3
C13 CHLORINATOR
C5
C14 BMS COOL/VENT INPUT
PUMP JUNCTION BOX
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
1
3
5
A1
T1 T2 T3 T4 T5 T6 T7
2
4
6 A2
L1
L2
FAN
MAINS SUPPLY
C1 Motor Contactor Coil
C7 Motor Control Signal
C2 Fuse T12.5a
C8 Wall Control
C3 Main PCB Power In
C9 Water Inlet Solenoid
C4 Pump Link
C10 Chlorinator Link
C5 Drain Valve
C11 Interface Board Link
C6 Salinity Probe
C12 Not Used
SEELEY INTERNATIONAL - INSTALLATION MANUAL |
200-240V / 3~ / 60Hz SUPPLY
INTERFACE PCB
DENOTES CLASS
2 CIRCUIT
C11
C13
C17
CHLORINATOR
C13
C16
C10
C15
C14
C12
C12
C4
gn/y
L3
861371-C
200-240V / 3~ / 60Hz SUPPLY
INTERFACE PCB
C11
C13
C17
C13
C16
C10
C15
C14
C12
C12
C4
C1 MOTOR CONTACTOR COIL
FUSE 3A
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
3
C8 WALL CONTROL
C9 WATER INLET SOLENOID
RELAY
C10 CHLORINATOR LINK
24VDC
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
5
C14 BMS COOL/VENT INPUT
8 7
C15 BMS ERROR SIGNAL OUTPUT
L3
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
BMS PUMP
AUX
ON/OFF
PUMP
C13 Chlorinator
C14 BMS Cool/vent Input
C15 BMS Error Signal Output
C16 BMS Remote On/Off
Input
C17 BMS Fan Speed Input
0-10Vdc
861371-C
865164-B
865164-B
17