MAINTENANCE INSTRUCTIONS cont.

CLEANING OR REPLACING INLET AIR FILTERS

The Inlet Air Filters should be and replaced as soon as the
airflow through the filters is restricted by dust or contaminants.
The frequency of changing the Inlet Air Filters is dependent on
the air quality at the site
Replacement Inlet Air Filters are available from SI Service
Agents and Climate Wizard Distributors. If alternative air filters
are supplied, they should be to EN779 G4 or ASHRAE 52.2
MERV8 standards as a minimum.
When ordering replacement Inlet Air Filters ensure the correct
sizes/part number for your cooler are selected from the tables
below.
Model
CW-H10
Replacement Kit
120423
P/No.
1 * 24x24x2in
(594x594x45mm)
Kit Contents
2 * 24x12x2in
(594x291x45mm)
To access the Inlet Air Filters, the front panel of the Air Filter
Cowling must be removed by releasing x2 quarter-turn
fasteners.
The Inlet Air Filters slide in and out of the Air Filter Frame.
When fitting, use the air flow direction sticker on the side of the
filter to ensure the correct orientation.
The smaller side and bottom filters slide into the filter frame. To
fit the larger front filter, locate the top edge of the filter under the
top brackets and lift to engage the filter inside them. Allow the
filter to drop, to engage the 2 bottom brackets at the bottom of
the frame.

CHANGING COOLER CORES

SIDE VIEWS
CW-H15, H15S, H15S Plus
120393
1 * 24x24x2in
(594x594x45mm)
3 * 24x12x2in
(594x291x45mm)
1.
2.
3.
4.
5.
6.
ILL2455-A
ILL2455-A
Cores
Core
Access
Panel
TOP VIEW
CORE AND SPREADER
ASSEMBLIES (LID REMOVED)
ILL1954-B
Power OFF, water OFF.
Disconnect and remove any fixed ducting from the exhaust
outlet of the cooler (if fitted).
Remove the exhaust transition/lid assembly from the
cooler.
Open the core access panels on either side of the cooler.
Remove the metal core clamp strips
LAY THE WATER SPREADER TRAYS
INTERCHANGE CORES THROUGH THE
Disconnect the spreader assembly from the rubber core
ACCESS PANEL OPENING.(BOTH SIDES)
(TEMPORARILY) FROM THE TOPS
extrusions and remove the water spreader assemblies.
They can be placed aside onto the lid of the cooler cabinet
OF THE CORES BACK ABOVE THE
while still remaining connected to the plumbing system.
ILL2462-A