Control Outputs Station Type Fc700A; Control Outputs Remote Station Type Ft700A; Modules - Siemens FC700A System Planning Manual

Fire detection system
Table of Contents

Advertisement

17.3

Control outputs station type FC700A

Basic equipment
B3Q700
CPU
E3G070
24V
Up to 2 Z3I1050 (with additional
terminal block) can be used other-
wise Z1K030 must be used.
17.4

Control outputs remote station type FT700A

B3Q700
17.5

Modules

Component
Order-No.
E3G070
546661
E3L020
546645
E3G050
460255
E3G060
542539
K3I110
528812
Z3B171
484383
E3I040
499310
Z1B070
A5Q00001720
Z3I1050
A5Q00004717
Z1K030
484231
Siemens Building Technologies
Fire & Security Products
Driver
Z3B171
1...............7
Z3B171
250VAC/10A
Fire control
installations
Z3I1050
E3I040
I-Bus
E3I040
converter
I-Bus/LON
LON-Bus
K3I110
1......16
30VDC/1A
Details mounting E3I040 see document 007827
Description
Control module 'Universal'
Control module 'Driver'
Control module 'Contacts'
Control module 'Monitored'
LON-I/O card
Relay module 1x 250VAC/10A
LON module
Mounting accessory for E3I040
Connection cable 19 conductors
Terminal block with p.c.b. Chassis
Additional control modules according to application
I-Bus
E3L020
E3G050
Driver
1..........16
1..........8
30VDC/1A
250VAC/10A
E3L020
K3I110
Notes
Included in FC700A-1 package
16 control inputs or outputs
8 control output contacts
6 monitored control lines for alarm equipment
16 programmable in-/outputs
To switch from external voltage
Converter between I-Bus and LON-Bus
Essential for mounting E3I040 in housing H28G200
1 of each per E3L020/E3G050/60
For direct connection
Control modules
E3I040
E3G060
Converter
Driver
I-Bus/LON
1..........6
LON-Bus
K3I110
1......16
30VDC/1A
Z1K030
Z3I1050
E3G070
E3G060
E3G050
E3I040
Z1B070
007836_a_en_--.doc
max. 24V/2A
(max. 4A/E3G060)
K3I110
41
03.2004

Hide quick links: