Detection Line "Collective" Synoline600/-Ex - Siemens FC700A System Planning Manual

Fire detection system
Table of Contents

Advertisement

15.4

Detection line "collective" SynoLINE600/-Ex

8 Stub lines
1
DBZ1197A
2
3
E3M080
8
OP620C
Siemens Building Technologies
Fire & Security Products
All detectors on a line have the same collective address (ZONE)
Number of detectors per line max. 25 with KMK1
Line termination depending on application by means of Transzorb or EOL22 (Ex)
Connectable types of detectors and connection see document 007831
DLO1191
DF1191/92
DM1103
SynoLINE600
DLR11 . .
SynoLINE600-Ex
DC1192
HI62xC
24VDC
Some detectors have different loading factors, to evaluate how many special de-
tectors can be connected to one collective line see chapter 16.2.
OP620C
HI62xC
DM1103
DO1101A-Ex
SB3
Line modules
Line termination: Transzorb 20V/EOL22
Line resistance: max.150Ω
DF1101-Ex
DT1101xA-Ex
Line termination
EOL22 (Ex)
007836_a_en_--.doc
37
03.2004

Hide quick links: