CommScope FL1000 User Manual
CommScope FL1000 User Manual

CommScope FL1000 User Manual

Rack-mount panel and wall-mount box

Advertisement

Quick Links

ADCP-90-545
Issue 4, July 2016
Rack-Mount Panel and Wall-Mount Box
Content
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1
UNPACKING AND INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2
RACK-MOUNT PANEL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1
2.2
2.3
2.4
3
WALL-MOUNT BOX INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1
3.2
3.3
3.4
4
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1
4.2
5
TECHNICAL ASSISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

INTRODUCTION

FL1000 products provide solutions for terminating and splicing fibers in small fiber networks. The
product line consists of three rack-mount panels and three wall-mount boxes. The rack-mount panels
include a 12-fiber termination panel, a 24-fiber termination panel, and a 24-fiber termination/splicing
panel. The wall-mount boxes include a 12-fiber termination/splicing box, a 24-fiber termination/
splicing box, and a 48-fiber splicing box. Options include 6pak adapter plates, with or without
pigtails, splice trays, and cable kits.
300001735123 Rev C
www.commscope.com
Installing a Rack-Mount Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1.1
19-Inch Rack, 5-Inch Recess (as Shipped) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1.2
Installing 6pak Adapter Plates and Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.2.1
Adapter Plates Without Pigtails (Blank or 6Pak) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2.2
Adapter Plates With Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installing Cables and Routing Fibers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.3.1
12-Fiber Termination Rack Mount Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3.2
24-Fiber Termination Rack Mount Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.3
24-Fiber Termination/Splicing Rack-Mount Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Splicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installing the Wall-Mount Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installing 6pak Adapter Plates and Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installing Cables and Routing Fibers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3.1
12-Fiber Termination/Splicing Wall-Mount Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3.2
24-Fiber Termination/Splicing Wall-Mount Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.3.3
48-Fiber Splicing Wall-Mount Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Splicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installing Patch Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Cleaning Adapters and Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
User Manual
FL1000
© 2016 CommScope. All Rights Reserved.
Page
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FL1000 and is the answer not in the manual?

Questions and answers

Summary of Contents for CommScope FL1000

  • Page 1: Table Of Contents

    TECHNICAL ASSISTANCE..............34 INTRODUCTION FL1000 products provide solutions for terminating and splicing fibers in small fiber networks. The product line consists of three rack-mount panels and three wall-mount boxes. The rack-mount panels include a 12-fiber termination panel, a 24-fiber termination panel, and a 24-fiber termination/splicing panel.
  • Page 2: Unpacking And Inspection

    ADCP-90-545 • Issue 4 • July 2016 This manual contains all procedures required to install and operate any FL1000 product or product option. The procedures are presented in the order in which they would normally be done, with separate installation sections for rack-mount and wall-mount units. Select from the procedures based on your specific installation.
  • Page 3: Rack-Mount Panel Installation

    Installing a Rack-Mount Chassis The FL1000 rack-mount panel can be installed on either a 19-inch (48.26 cm) or 23-inch (58.42 cm) rack. It is designed for mounting in an EIA style rack, but a WECO style rack can also be used. It can be mounted flush on the rack or with a 5-inch (12.7 cm) recess.
  • Page 4: 19-Inch Rack, Flush; 23-Inch Rack, 5-Inch Recess; 23-Inch Rack, Flush

    R RA FOR 5-INCH PO SU DIA TIO RE TO BE AM RECESS MOVE MOUNTING BRACKETS TO THIS 11248-C POSITION FOR FLUSH MOUNT Figure 2. Installing a Chassis on a 23-Inch Rack Page 4 © 2016 CommScope. All Rights Reserved.
  • Page 5: Installing 6Pak Adapter Plates And Pigtails

    2. Align the adapter plate tabs with the notches in the mounting slot as shown in Figure 3. Slide the 6pak or blank up into the slot until it snaps in place. SLOT SPLICE DECK 11418-B 6 PAK PLATE (LOADED) Figure 3. Installing 6pak Plates Page 5 © 2016 CommScope. All Rights Reserved.
  • Page 6: Adapter Plates With Pigtails

    Figure 5. To tie the fibers, use cord lacing. 6. Route the fibers to the splice tray. For an illustration of correct routing, refer to subsection 3.4, Splicing, below. Page 6 © 2016 CommScope. All Rights Reserved.
  • Page 7 TOP VIEW WITH SPLICE DRAWER CLOSED PROPER BEND RADIUS MUST BE MAINTAINED TIE DOWN USING CORD LACING 11434-B TOP VIEW WITH SPLICE DRAWER OPEN Figure 5. Correct Pigtail Routing within 24-Fiber Termination/Splicing Module Page 7 © 2016 CommScope. All Rights Reserved.
  • Page 8: Installing Cables And Routing Fibers

    7. Connect the fiber connectors to the adapters on the rear of the 6pak adapter plate. 8. Slide in the bulkhead deck to its closed position. 9. Replace the front access cover. Page 8 © 2016 CommScope. All Rights Reserved.
  • Page 9 CABLE ENTRY FROM RIGHT TIE OFF USING TIE-DOWN BRACKET SUPPLIED WITH PANEL TIE DOWN ON OPPOSITE SIDE FROM ENTRY USING CORD LACING SECURED ON LANCE 11246-D Figure 6. Cable Breakout for 12-Fiber Panel Page 9 © 2016 CommScope. All Rights Reserved.
  • Page 10: 24-Fiber Termination Rack Mount Panel

    LACING CABLE ENTRY FROM RIGHT TIE DOWN USING CORD LACING 11245-E Figure 7. Cable Breakout for 24-Fiber Panel Use the following procedure to install a cable in the 24-fiber termination rack-mount panel. Page 10 © 2016 CommScope. All Rights Reserved.
  • Page 11 4. Remove the rear door, if not already removed. 5. Route the fibers within the chassis as shown in Figure 7 and tie down the fibers in the B position shown. Page 11 © 2016 CommScope. All Rights Reserved.
  • Page 12: 24-Fiber Termination/Splicing Rack-Mount Panel

    5. Tie the fibers down with cord lacing in the B position shown in Figure 6. If the cable being installed is an OSP cable with a metallic strength member, bond the cable to ground following the instructions for the bonding/grounding kit. Page 12 © 2016 CommScope. All Rights Reserved.
  • Page 13 TIE DOWN CABLE ON OPPOSITE SIDE FROM ENTRY TO BRING CABLE IN FROM RIGHT REAR, ROUTE CABLE COUNTER-CLOCKWISE. ALSO, REMOVE AND REROUTE PIGTAILS COUNTER-CLOCKWISE 11232-D Figure 9. Fiber Routing in 24-Fiber Termination/Splicing Panel Page 13 © 2016 CommScope. All Rights Reserved.
  • Page 14: Splicing

    Note: If using a cable clamp (as opposed to a compression fitting), install the cable clamp prior to mounting the box on the wall. FL1000 wall-mount boxes can be mounted directly to any wall, but CommScope recommends that they be mounted, using the #12 woodscrews supplied with the unit, on a 3/4-inch thick plywood panel that is attached to the wall in accordance with local fire code.
  • Page 15 (10.7 CM) 10.07 IN. TOP VIEW (25.6 CM) MOUNTING HOLE (4 PLACES) FRONT VIEW 11.23 IN. (28.5 CM) 8.23 IN. (20.9 CM) 24562-A 12.80 IN. (32.5 CM) Figure 11. 12-Fiber Wall-Mount Box Dimensions Page 15 © 2016 CommScope. All Rights Reserved.
  • Page 16 (10.7 CM) 10.07 IN. TOP VIEW (25.6 CM) MOUNTING HOLE (4 PLACES) FRONT VIEW 15.00 IN. (38.1 CM) 12.00 IN. (30.5 CM) 24563-A 12.80 IN. (32.5 CM) Figure 12. 24/48 Wall-Mount Box Dimensions Page 16 © 2016 CommScope. All Rights Reserved.
  • Page 17: Installing 6Pak Adapter Plates And Pigtails

    Figure 13 below. END TAB PIGTAILS SLOT 24565-A 6 PAK PLATE (LOADED) END TAB Figure 13. Installing a 6Pak Plate with Pigtails in a Wall-Mount Box Page 17 © 2016 CommScope. All Rights Reserved.
  • Page 18 4. If installing pigtails, route the fibers within the chassis corresponding to Figure 14 Figure 15 for the 12-fiber and 24-fiber termination/splicing panel, respectively. 24569-A Figure 14. Pigtail Routing in 12-Fiber Termination/Splicing Panel 24568-A Figure 15. Pigtail Routing in 24-Fiber Termination/Splicing Panel Page 18 © 2016 CommScope. All Rights Reserved.
  • Page 19: Installing Cables And Routing Fibers

    19.0 IN. (114.3 CM) (48.3 CM) IFC OR OSP CABLE SHEATH SUB-UNITS FIBERS RADIUS ROUTED LIMITERS CONNECTORS FROM TOP 24570-A Figure 16. Field Termination Breakout and Routing, 12-Fiber Wall-Mount Box (Top Entry) Page 19 © 2016 CommScope. All Rights Reserved.
  • Page 20 19.0 IN. (114.3 CM) (48.3 CM) IFC OR OSP CABLE SHEATH SUB-UNITS FIBERS RADIUS LIMITERS CONNECTORS 24573-A ROUTED FROM BOTTOM Figure 17. Field Termination Breakout and Routing, 12-Fiber Wall-Mount Box (Bottom Entry) Page 20 © 2016 CommScope. All Rights Reserved.
  • Page 21 RADIUS LIMITER PLACE GROMMETS ON EACH RADIUS LIMITER BEHIND AND IN FRONT OF SPLICE TRAY CORNER OF SPLICE TRAY 24578-A ROUTED FROM BOTTOM Figure 18. Splicing Breakout and Routing, 12-Fiber Wall-Mount Box Page 21 © 2016 CommScope. All Rights Reserved.
  • Page 22 Assemble the cable clamp components on the integral bolts in the order shown in the figure and secure with the two nuts provided. CLAMP BRACKET INTEGRAL BOLTS CLAMP 24566-A YOKES (2) PLATE RUBBER GROMMET NUTS (2) Figure 19. Cable Clamp Assembly (Select from Four Mounting Locations) Page 22 © 2016 CommScope. All Rights Reserved.
  • Page 23 Figure 20. Compression Fitting (Select from Eight Mounting Locations) 5. If the cable being installed is an OSP cable with a metallic strength member, bond the cable to ground following the instructions for the bonding/grounding kit. Page 23 © 2016 CommScope. All Rights Reserved.
  • Page 24: 24-Fiber Termination/Splicing Wall-Mount Box

    RADIUS LIMITERS ROUTE BOTTOM THREE FIBERS AROUND LEFT RADIUS LIMITER ONLY TOP 6 PAKS 24574-A (ROUTED FROM TOP) Figure 21. Field Termination Breakout and Routing, 24-Fiber Wall-Mount Box (Top Entry, Top 6paks) Page 24 © 2016 CommScope. All Rights Reserved.
  • Page 25 FIBERS RADIUS LIMITERS ROUTE BOTTOM FIBERS AROUND LEFT RADIUS LIMITER ONLY 24576-A BOTTOM 6 PAKS (ROUTED FROM TOP) Figure 22. Field Termination Breakout and Routing, 24-Fiber Wall-Mount Box (Top Entry, Bottom 6paks) Page 25 © 2016 CommScope. All Rights Reserved.
  • Page 26 RADIUS LIMITERS ROUTE BOTTOM THREE FIBERS AROUND LEFT RADIUS LIMITER ONLY 24575-A TOP 6 PAKS (ROUTED FROM BOTTOM) Figure 23. Field Termination Breakout and Routing, 24-Fiber Wall-Mount Box (Bottom Entry, Top 6paks) Page 26 © 2016 CommScope. All Rights Reserved.
  • Page 27 FIBERS RADIUS LIMITERS ROUTE BOTTOM FIBERS AROUND LEFT RADIUS LIMITER ONLY 24577-A BOTTOM 6 PAKS (ROUTED FROM BOTTOM) Figure 24. Field Termination Breakout and Routing, 24-Fiber Wall-Mount Box (Bottom Entry, Bottom 6paks) Page 27 © 2016 CommScope. All Rights Reserved.
  • Page 28 AND IN FRONT OF SPLICE TRAY CORNER OF SPLICE TRAY 24578-A ROUTED FROM BOTTOM Figure 25. Splicing Breakout and Routing 24-Fiber Wall-Mount Box Use the following procedure to prepare and install the cable. Page 28 © 2016 CommScope. All Rights Reserved.
  • Page 29: 48-Fiber Splicing Wall-Mount Box

    If from top and bottom, then an “S” curve, under the splice tray, must be used to reverse the direction of one cable so that they may both enter the splice tray from the bottom. Page 29 © 2016 CommScope. All Rights Reserved.
  • Page 30 PLACE GROMMETS ROUTED FROM TOP ON EACH RADIUS LIMITER BEHIND AND IN FRONT OF SPLICE TRAYS CORNER OF SPLICE TRAYS 24581-A ROUTED FROM BOTTOM Figure 26. Routing within 48-Fiber Splicing Wall-Mount Box Page 30 © 2016 CommScope. All Rights Reserved.
  • Page 31 This practice also helps prevent contamination of connectors and adapters. 7. Refer to subsection 3.4, Splicing, below, for splicing instructions. Page 31 © 2016 CommScope. All Rights Reserved.
  • Page 32: Splicing

    6. Place the splice trays back in the splice deck and place grommets on the radius limiters above the splice trays to hold it in place within the splice deck (see Figure 26 insert). Figure 27. Routing Fibers on a Splice Tray Page 32 © 2016 CommScope. All Rights Reserved.
  • Page 33: Operation

    2. Open the front cover and connect patch cords at the applicable receptacles on the bulkhead panel. 3. Route the patch cords in the direction of the angled adaptor toward the side of the FL1000 unit and then to office equipment (interconnect) or another FL1000 unit (cross-connect).
  • Page 34: Technical Assistance

    ADCP-90-545 • Issue 4 • July 2016 5 TECHNICAL ASSISTANCE Contact the Technical Assistance Center (TAC) for technical question. Call 800.830.5056 or send an email to TAC.Americas@commscope.com. Page 34 © 2016 CommScope. All Rights Reserved.

Table of Contents