Siemens BACnet Heat Pump Controller - Multi-Stage Owner's Manual
The mixed air loop controls only the mixed air portion of the application.
The mixed air damper motor can be either a spring return or floating control damper motor.
For a spring return damper, the mixed air loop will control the damper through its 0 to
10 volt analog output and the digital outputs will be spare.
For a floating control damper the mixed air loop will control the damper through DO 1
and DO 2, and the analog output will be a spare.
Day Mode – When heating is required and the fan is on, the damper is set to minimum
position. If the fan is off, the damper is closed.
When cooling is required the damper will be modulated by the mixed air temperature control
loop. Damper position will not be set below minimum position to make sure that the
ventilation requirements are being met.
Night Mode – The damper is closed (0%) during night mode when cooling is not required
and/or mixed air control is not used at night.
Mixed Air Control - When cooling is required the damper will be modulated by the mixed air
temperature control loop.
If the cooling loop is between the limits for free cooling and all other conditions have been
met for enabling the mixed air loop, control depends on the following:
If the cooling loop was previously higher than free cooling, the mixed air loop will
remain enabled.
If the cooling loop was previously lower than free cooling, the mixed air loop will
remain disabled.
NOTE:

Calibration

Floating Control Damper – The damper is briefly commanded closed to get an accurate
damper position during calibration.
8
CAUTION:
This application does not have built in low temperature detection for the mixed
air dampers. The low temperature detection is handled differently depending on
what type of damper is used (spring return or floating control).
Stand-alone low temperature detection is not possible with floating control
dampers. A program can be written in the field panel to close the damper when a
low temperature situation occurs. Contact your local Siemens Building
Technologies representative for more information.
This can happen in day or night mode.