Siemens BACNET 125-699 Owner's Manual page 28

Heat pump controller – multistage
Table of Contents

Advertisement

Siemens BACnet Heat Pump Controller - Multi-Stage Owner's Manual
Description
Address
Dl OVRD SW
{19}
OVRD TIME
20
NGT OVRD
{21}
RMTMP OFFSET
22
FREE CLG
{23}
DI 2
{24}
DI 5
{25}
DI 6
{26}
CMP2 MlN OFF
27
HTG2 MlN OFF
27
CMP2 MlN ON
28
HTG2 MlN ON
28
20
Application
2583, 2584, 2590
Actual indication of the status of the override switch (not
physically available on all temperature sensor models) at the
room temperature sensor. ON indicates that the switch is
being pressed. OFF indicates that the switch is released.
Valid input: ON or OFF
2583, 2584
Amount of time in hours that the controller will operate in
day/occupied mode when the override switch is pressed
while the controller is in night/ unoccupied mode.
2583, 2584
Indicates the mode that the controller is operating in with
respect to the override switch. NIGHT indicates that the
switch has not been pressed and the override timer is not
active. DAY indicates that the switch has been pressed and
the override timer is active. The controller then uses a day
mode temperature setpoint. This point is only in effect when
DAY.NGT indicates night mode.
All
Compensates for deviations between the value of ROOM
TEMP and the actual room temperature. This corrected
value is displayed in CTL TEMP.
RMTMP OFFSET + ROOM TEMP = CTL TEMP
2583, 2584
Point commanded by the field panel PPCL to enable or
disable mixed air control (free cooling).
2583, 2584, 2590
Actual status of a contact connected to the controller at Dl 2.
ON indicates that the contact is closed; OFF indicates that
the contact is open. If a wall switch is used, it is connected
to DI 2. See WALL SWITCH.
2583, 2584, 2590
Actual status of a contact connected to the controller at
Al 5/Dl 5. ON indicates that the contact is closed; OFF
indicates that the contact is open. When a contact is
connected at Dl 5, Al 5 is not available. See Point number
15. The physical input can not be used for both analog and
digital input at the same time.
2583, 2584, 2590
Actual status of a contact connected to the controller. ON
indicates that the contact is closed; OFF indicates that the
contact is open. Application 2583/2584: DI 6 can be used to
monitor an input that changes state when the heat pump is
in alarm. DI 6 can be unbundled to send alarm information
to the field panel for centralized alarm monitoring.
2583
Minimum time, in minutes, that compressor 2 will remain
OFF before turning ON.
2584
Minimum time, in minutes, that heating compressor 2 will
remain OFF before turning ON.
2583
Minimum time, in minutes, that compressor 2 will remain ON
before turning OFF.
2584
Minimum time, in minutes, that heating compressor 2 will
remain ON before turning OFF.
Description
Siemens Building Technologies, Inc.