Siemens BACNET 125-699 Owner's Manual page 30

Heat pump controller – multistage
Table of Contents

Advertisement

Siemens BACnet Heat Pump Controller - Multi-Stage Owner's Manual
Description
Address
DO 1
{41}
DO 2
{42}
DO 3
{43}
ELEC HEAT
{43}
ELEC HEAT 1
{43}
DO 4
{44}
HTG CMP 1
{44}
REV VALVE
{44}
DO 5
{45}
COMPRESSOR 1
{45}
HTG CMP 2
{45}
CLG CMP 1
{46}
DO 6
{46}
EHEAT3.CMP2
{46}
CLG CMP 2
{47}
DO 7
{47}
EHEAT2.CMP3
{47}
DMPR COMD
{48}
MTR1 COMD
{48}
22
Application
2583, 2584, 2590
Digital output 1 controls a 24 Vac load with an ON or OFF
status. If Motor 1 is enabled, DO 1 is coupled with DO 2 to
control an actuator.
2583, 2584, 2590
Digital output 2 controls a 24 Vac load with an ON or OFF
status. lf Motor 1 is enabled, DO 2 is coupled with DO 1 to
control an actuator.
2590
Digital output 3 controls a 24 Vac load with an ON or OFF
status. lf Motor 2 is enabled, DO 3 is coupled with DO 4 to
control an actuator.
2584
This output controls the contact for the first stage of electric
heat and has a status of ON or OFF.
2583
This output controls the contact for the first stage of electric
heat and has a status of ON or OFF.
2590
Digital output 4 controls a 24 Vac load with an ON or OFF
status. lf Motor 2 is enabled, DO 4 is coupled with DO 3 to
control an actuator.
2584
Digital output used to control the heating compressor 1.
2583
Digital output used to control the reversing valve.
COOL and HEAT status is indicated for the 24 Vac valve or
relay. The default configuration is energized for HEAT. The
configuration may be reversed in DO DIR.REV.
2590
Digital output 5 controls a 24 Vac load with an ON or OFF
status. lf Motor 3 is enabled, DO 5 is coupled with DO 6 to
control an actuator.
2583
Digital output used to control the compressor. ON or OFF
status is indicated for the 24 Vac relay.
2584
Digital output used to control heating compressor 2. ON or
OFF status is indicated for the 24 Vac relay.
2584
Digital output used to control cooling compressor 1.
2590
Digital output 6 controls a 24 Vac load with an ON or OFF
status. lf Motor 3 is enabled, DO 6 is coupled with DO 5 to
control an actuator.
2583
Digital output used to control either compressor 2 or the
third stage of electric heat.
2584
Digital output used to control cooling compressor 2.
2590
Digital output 7 controls a 24 Vac load with an ON or OFF
status.
2583
Digital output used to control either compressor 3 or 2nd
stage of electric heat.
2583, 2584
Value to which the damper motor is commanded in percent
of full travel.
2590
Value to which the Motor 1 actuator is commanded in
percent of full travel.
Description