processor Run or Program mode. If the owner ControlLogix processor is in
Program Mode, the 1757-ABRIO is in program mode (even if the ABRIO is
receiving messages). If the ControlLogix processor is in Remote Test mode,
the remote I/O mode for the 1757-ABRIO is program.
The remote I/O mode is not affected by the operating mode of a
ControlLogix processor that has an input only connection to the 1757 ABRIO.
In the absence of an exclusive owner connection, the 1757-ABRIO remote
I/O mode is determined by whether it is receiving messages, as before.

Add a Module as an Exclusive Owner Connection

To configure the 1757-ABRIO in RSLogix 5000, ControlLogix must be
offline.
1. If you are creating a new project, select File/New to create a new
project, give the processor a name, and enter the slot it occupies in the
ControlLogix rack.
2. Right click on I/O configuration and select New Module...
3. Select a module of Type 1756-MODULE Generic 1756 Module from
the list and Click OK.
RSLogix 5000 displays the Module Properties - Local:slot
(1756-MODULE 1.1) dialog box displays.
Figure 5.1 Module Properties Dialog 1
4. Assign the module a Name and a Description, if desired.
5. Set the Slot to match the slot number of the module in the chassis.
6. Select Comm Format Data - INT - With Status.
AB Spares
Configuring ControlLogix to Access Data on the 1757-ABRIO
Publication 1757-UM007C-EN-P - April 2004